8of10 MN301200 RevA
WIRING StepFive
ELECTRICALCONNECTIONS:
TheLV41andLV42seriesfeatureaSPDTrelaycontact.SPDT,singlepoledoublethrowallowsforoperationof
both increasing and decreasing level, depending on the connections made between the terminals of the
microswitchandthecable.SPDT,whichisathreeconductorcable,hasoneleadthatiscommon,onethatis
normally open (NO), and the other that is normally closed (NC). For the proper connections of these
conductorspleaserefertothewiringdiagramsbelow.
NCWiring:
TheNormallyClosed(NC)wiringistypicallyusedforafillingoperation.Thecontactwillcloseatalowlevel
andopenatahighlevel.
NOWiring:
TheNormallyOpen(NO)wiringistypicallyusedforanemptyingoperation.Thecontactwillcloseatahigh
levelandopenatalowlevel.
Warning:Whenmakingtheconnectionsdescribedabove,ensurethatthemaximummotor
powerdoesnotexceedthevaluesindicatedonthelevelswitch.Thepowersupplycableis
animportantpartofthesumpfloat.Shouldthecableappeartobedamaged,discontinue
useimmediatelyandproceedtoreplacetheunit.Theterminalusedmustalsobeprotected
againstaccidentalbreak.Also,correctlyinsulateanywirenotinuse.